- Product Brief
JJ1 series motor starting cabinet is designed and manufactured according to the national standard GB7251.1 "Low-voltage switchgear and control equipment" and conforms to the International Electrotechnical Commission IEC298 "AC metal closed switchgear and control equipment" standard, meeting the DL402, DL404 standards. This series of products use autotransformer to compensate the voltage drop when starting the motor, and at the same time equipped with motor comprehensive protector. When the motor is out of phase or overloaded due to some reason, it can cut off the power supply in time to avoid the burning of the motor to the greatest extent.
Two. Scope of application
This product is suitable for the three-phase squirrel cage induction motor with rated voltage 380V, rated frequency 50Hz, rated current 250A (135KW) and below to do not frequently step-down starting and stopping.
Three. Working conditions
Power supply voltage: 380 + 10%, 50Hz
Applicable motor: three phase squirrel cage asynchronous motor
Medium temperature: - 15 C ~ +40 C
Medium humidity: 90% no frost.
Starting frequency: no more than 12 hours per hour, and the starting interval is longer than 5 minutes.
Place of use: There is no explosive dangerous medium in the room, and there is not enough gas and conductive dust to corrode metal and destroy insulation in the medium. The ventilation is good.